Designed for the monitoring of hydrocarbon fluids separators, the alarm device NIVOIL may be connected to 1, 2, or 3 sensors.
- Hydrocarbon layer thickness sensor to detect when the maximum thickness is reached.
- Overfill sensor to detect when the fluids are on the highest level.
- Sludge layer sensor for alarming when maintenance is necessary.
The 3 sensors may be connected to any input of the alarm device NIVOIL. Any combination of the sensors can be wired. The instrument recognizes automatically the level sensor type. A LED indicates the sensor type on the diagram on the front board. The alarm device NIVOIL has a built-in buzzer; it is possible to disable its function.
Low power consumption
This model working with a 10 to 27 V DC power supply has low energy consumption. It is designed for the use of a solar-powered battery or any standard electric battery (consumption is 0.1 W – 12 V DC – with 3 sensors connected with one complete control cycle per hour).
Sleep mode
This model is adjustable by modifying the frequency of the control cycle (from 6 minutes up to 9 days). A continuous control mode could be switched on when there is no limit on consumption.
ATEX certified
All the components are ATEX certified. The sensors are for a location in zone 0 and the alarm device corresponds to zone 2.
Features
- Low power consumption - 10...27 V DC power supply input
- Zone 0 ATEX certified (Zone 2 for the alarm device location)
- Solar-powered or standard electric battery - Energy saving mode adjustable (control frequency adjustable from 6 min up to 9 days)
- 3 inputs, for any NIVOIL probes
- Automatic recognition of type probe
- 3 relay outputs with an audible alarm
Another Article: |
Specification
Main power supply: | 10...27 V DC |
Power consumption: | 0.1 W / 12 V DC (3 sensors connected and 1 control cycle per hour) |
Housing protection: | IP65, according to EN 60529 |
Temperature limits: | -20...+60°C |
Sensor inputs: | 3 inputs with automatic sensor type detection |
for hydrocarbon fluids layer thickness, overfill level, sludge layer level | |
Monitoring: | The alarm device NIVOIL has an auto-diagnostic of measuring loop |
a short circuit or a broken cable. | |
Display and signals: | 1 function signal LED (green) on each channel |
1 alarm signal LED (red) on each channel | |
Built-in audible alarm, disabled by DIP switch configuration | |
Front panel: | 2 push buttons for diagnostic test and alarm clearance |
Outputs: | 3 relay outputs, Power switch 250 V AC as a maximum / 3A, Potential free change over contacts |
ATEX Certificate: | BVS 10 ATEX E 011 / The alarm device may be mounted in Ex area, zone 2 |
Ex protection class: | II 3 (1) G Ex NAC [ia Ga] IIB / IIA T4 Gc (Intrinsic safety) |
CE Marks | According to EC directives (72/23/EEC), Low Voltage Guidelines: RL 2006/95/EG & RL93/68/EWG, |
EMV Guidelines: RL 89/336/EWG (EN 61326) | |
ATEX | RL 94/9/EG (ATEX 95) |
EN 60079-0 (General requirements) - EN 60079-11 (Intrinsic safety) - EN 60079-26 (Group II; category 1G) |
Download Data Sheet: Alarm System for Oil-Water Separators NivOil®/ 12 V dc
Ref: bamo.eu