Flow measurement provides a variety of application-specific challenges because each has individual measurement requirements, restrictions, piping considerations, etc. FLO-CORP’s experienced team is second-to-none when providing expert flow advice on the correct meters for your application. Our team will help you navigate through the selection process if you are not sure which meter to use. Technologies offered include variable area, positive displacement, ultrasonic, magnetic, mass, and open channel flow meters.
Three defining traits of our MEMFlo Variable Area line of flow meters are easy installation, accuracy, and low maintenance. So durable and reliable, most last over 30 years. These meters are no ordinary volumetric flow meters. With an excellent tolerance to suspended solids, no need for straight runs of pipe, and over thirty years of tried and true use in harsh applications, these flowmeters rightly hold their place as our flagship model.
The MFT2™ two-wire flow transmitter accurately calculates and outputs the flow rate. Compatible with any MEMFlo variable area flow meter, MFT2™ combines FLO-CORP’s time-proven variable area technology with a high tech processor and solid-state circuitry. Each device includes an analog output that can be configured for 0-5 VDC, 0-10 VDC, or 4-20 mA current loop. Typical applications include pump flow output, compressed air consumption, cooling flow monitoring, steam flow usage/optimization and combustion gas metering.
Features and Benefits
- Non-contact sensor electronic
- Electronic signal conditioning circuit
- 3 output modes: 4-20mA, 0-5 VDC or 0-10 VDC
- Proportional analog output - two-wire, 4-20mA
- Designed to slip over any standard measuring tube
- Pre-calibrated from the factory for fast installation and start-up
- Optional Epoxy Coated Aluminum Enclosure for durable, rugged applications
Specifications
General | |
Process Temperature | F: -20º to 240º C: -29º to 116º |
Ambient Temperature | F: -20º to 158º C: -29º to 70º |
Environmental | Humidity: 0-90% non-condensing |
Accuracy | ±1% 0.25% rate |
Repeatability | ±0.10% rate |
Electrical | |
Power Requirements |
0.5 VDC Output 10-30 VDC @ 3 wire 0-10 VDC Output 12-30 VDC @ 3 wire 4-20 mA Output loop-powered, 12 VDC - 30 VDC - 2 wire |
Power Consumption | 25 mA maximum |
Analog Outputs | 0-5 VDC and 0-10 VDC into 10,000 Ohms minimum; 4-20 mA into 1000 Ohms maximum |
Resolution | 1:4000 |
Transmission Distance | 4-20 mA limited by cable resistance (4000’) 0-5 VDC 1000 feet (330m) maximum 0-10 VDC 1000 feet (300m) maximum |
Circuit Protection | Reverse polarity and current limiting |
Isolation | Inherently isolated from the piping system |
Transient Over-Voltages | Category 3, in accordance with IEC 64 |
Temperature Drift | 50 ppm/ºC (Max) |
Enclosure Rating | NEMA 4 (IP67) ; NEMA 7, Aluminum |
Download Datasheet: MEMFlo™ Universal MFT2 2-Wire Flow Transmitter