Delta Elektrogas VMR 60 Safety solenoid valves

Gas Solenoid Valve | VMR60 electrogas Flow control

VMR 60 Solenoid Valve

Delta Elektrogas VMR 60 Safety solenoid valves

Safety solenoid valves 
for air and gas, fast opening and fast closing type
DN8 - DN150

The VMR type valve is a fast opening single-stage solenoid valve, normally closed (open when energized). This type of device is suitable for air or gas blocking and releasing controls, required in gas power burners, atmospheric gas boilers, industrial kilns and other gas-consuming appliances.

Baca juga: Elektrogas automatic safety solenoid valves

Function and Application

The VMR type valve is a safety shutting device using the auxiliary power supply. When it is de-energized, the spring pushes on the seal disc, keeping the gas passage closed. Now, the inlet chamber is under the gas line pressure which forces on the disc, increasing the closing function and improving the seal.

When the coil is powered the valve opens rapidly, against the strength of the spring and gas pressure. The flow may be adjusted using the regulating screw on the top (see the installation and service instructions). If the power supply is shut off, the valve rapidly closes, interrupting the gas flow

Delta Elektrogas VMR 60 Safety solenoid valves

Specification

ConnectionsInternal threaded ISO 7-1 from Rp1/4 to Rp2½
ANSI-ASME B1.20 from 1/4” NPT to 2”½NPT
Flanged ISO 7005 PN16 from DN40 to DN150
ANSI-ASA-ASME B16.5 class 150 from 2” to 6”
Voltage ratings230 VAC 50/60 Hz
120 VAC 50/60 Hz
110 VAC 50/60 Hz
24 VAC/DC
12 VAC/DC
Voltage tolerance-15% to +10%
Temperature-15°C to +60°C  (+5°F to +140°F)
Max. operating pressure200 mbar (3 psig)
360 mbar (5 psig)
500 mbar (7 psig)
6 bar * (90 psig)
Body test pressure1 bar (15 psig)
9 bar * (130 psig)
Closing time< 1 second
Opening time< 1 second
Gas strainer600 µm (0.02 in) (except brass models and 6 bar)
EnclosureIP54 (NEMA 3), optional IP65 with cable (NEMA 4)
Cable glandM20x1,5 for terminal box
PG 9 for ISO plug
Wires cross-section2,5 mm2 max. (AWG 12) for terminal board
1,5 mm2 max. (AWG 14) for ISO plug
Electrical safetyClass I (EN 60335-1)
Coil winding insulationClass H (200°C, 392°F)
Coil thermal resistanceClass F (155°C, 311°F)

Data Sheet Elektrogas-VMR

Visit Wmablog for more info