KEP meter Intellect-69PM2 (INT69PM2) Process Monitor with Analog Inputs

 
The Intellect-69PM2 is a process monitor that accepts analog signal inputs and has a featuring
41/2 digits of bright, 7-segment LED displays. The unit can be field programmed to accept
0-20mA, 4-20mA, 0-5V, 0-10V or 1-5V signals.


Two assignable setpoints are standard for high/low alarm outputs. The high and low scaling settings (-9999 to 49999) are programmable from the front panel. By pressing the “view” button, the unit will display process reading, peak, or valley.

Press the lock button once to freeze the display, and press it again to resume normal operation.
Press the lock button 4 times quickly to enter the lock code for panel lockout. RS-232, RS-422, and
4-20mA analog out are available options for interfacing with a host computer or strip chart recorder.

Feature :

  • Analog Input 0-20 mA, 4-20 mA 0-5V, 0-10V or 1-5V
  • Display Rate, Pressure, Level, Temperature, Watts, etc., Peak & Valley
  • Calibration, High and Low Values (-9999 to 49999) Fully Programmable Through Keypad
  • NEMA 4X / IP65 Front
  • +24V Output for Peripherals
  • 16 Bit A/D Resolution
  • 2 Form C SPDT Relays (optional)
  • 2 Levels of Operator Password Lockout

Application: Any process monitoring application where two set points and scaling are needed.

Specification :

Display

41/2 digit, .55” high, 7 segments, red-orange, LED.

Input Power

110, 220 VAC ± 15% or 12 to 24VDC.
Current:300 max. mA DC or 10.0 VA (10W) at rated AC voltage.

Output Power

(AC-powered units only) + 24VDC @ 50mA regulated ±5%.
(100 mA available on request)

Temperature

Operating: +32°F (0°C) to +130°F (+54°C).
Storage: -40°F (-40°C) to +200°F (93°C).

Memory

EEPROM stores data for ten years if power is lost.

Reset

Front Panel: resets displayed value and control outputs.

Control Outputs

Standard: Open collector sinks 250mA from 30VDC when active.
Optional: 2 each Form C SPDT 5 Amp @ 120/240 VAC or 28 VDC.

Input

Linear 0-20mA, 4-20mA, 0-5V, 0-10V or 1-5V selectable from the front panel.

Calibration

The unit does all of the calibrations internally. There are no potentiometers
to adjust and the unit never needs to be removed from the case or panel.

Set Points

Two control setpoints are provided. The unit comes standard with two open
collector control outputs. Two 5 Amp, Form C relays are optional.
The outputs have a programmable alarm range from -9999 to 49999 with hysteresis.

Process Display

Updates 4 times per second, accurate to 4.5 digits.

Programming

Decimal points, Scaling from -9999 to 49999, setpoints, input type,
and security lock code are all programmable from the front panel.

Housing

Standard 1/8 DIN, high-impact ABS plastic case (NEMA 4X/IP65 front panel).

Shipping Weight

2 lbs.

Overvoltage Protection

50 V

Over-current Protection

50 mA

Temperature Stability

Will not drift more than 10 parts per million per °C from 0°C to 54°C

Accuracy

1% (5 V inputs .16%)

Listing

CE Compliant, CSA (File No. LR91109), NRTL/C pending




For more info and price please contact us, at marketing@wmablog.com