Eska EGV Manual Reset Gas Valve Gas Networks and Industrial Pipelines

50 years ago, all started in a small mold workshop. over the years, Eska product portfolio and production capacity have expanded. Ingenuity, hard work and commitment to manufacture reliable products transformed that small workshop into a factory, fully capable of producing any of the components of our product portfolio independently.  Eska  proudly declare that our evolving structure and constant growth led us to be the market leader in Turkey and Internationally recognized brand in global scale.

Eska have some categories of product such as Direct Acting Gas Pressure Regulators, Double Stage Gas Pressure Regulators, Single Stage Gas Pressure Regulators, Gas Filters, Gas Valves, Natural Gas LPG Gas Alarm Device. And Eska have some solution for gases. Such as Cabinet Solutions and Station Solutions.

EGV Manual Reset Gas Valve Gas Networks and Industrial Pipelines

ESKA Series EGV Manual Reset Gas Valve Gas Networks and Industrial Pipelines, manually adjusted gas valves, are used for  safety purposes in the gas lines to automatically stop the gas flow by the effect of the signals given by the third party equipment such as gas alarm detectors, ventilation devices etc. These are the manually adjusted gas valves used with the safety purposes in the gas lines to automatically stop the gas flow by the effect of the signals given by the third party equipment such as gas alarm detectors, ventilation equipment etc.

Features

  • Manually adjusted gas valves
  • The safety purposes in the gas lines to automatically stop the gas flow

Another Article:

Specification

UsageCity gas networks and gas pipelines in industrial areas
MediumNatural Gas (Methane), LPG, Town Gas, Air, etc…
PositionNormally Open
Connection or Port Size1/2”, 3/4, 1”, 11/4”, 11/2”, 2” Threaded (Female), DN65, DN80 DN100 Flanged
Maximum Working Pressure0,5 bar
Working Voltage Range12V, 220V AC or DC (On request other voltages)
Ambient Temperature Range‐20°C up to 60°C
Protection ClassIP54
Voltage Tolerance± %10
Response TimeLess than 1 second
ResetManually
Material StandardAluminum-EN 1706 / Rubber-EN 549

Download Data Sheet: EGV Manual Reset Gas Valve Gas Networks and Industrial Pipelines

Ref: en.eskavalve.com