Flowma TGF06C-A Thermal Mass Flowmeter

 

Flowma TGF06C-A Thermal Mass Flowmeter

Flowma TGF06C-A is based on thermodynamic principle, can measure air velocity and air volume, there are 2 temperature sensors inside the probe:one for temperature measurement, the other one as a measuring conveyor after heated. Temperature difference between the two as a basis for measuring flow rate. When the medium flow rate increases, the temperature difference decreases. The temperature difference converted to standard signal output a fter processed that is why flow rate can be measured by these two sensors. All-metal housing, suitable for a variety of pipe diameters.

Feature

  •  Thermal mass flow, quickly response, good sensitivity
  • Turndown ratio 500:1, high precision & accurate sensing at lowest flow rate for metering applications
  • Display Instantaneous flow, the cumulative flow can be displayed in the software
  • Output:Analog / RS-485
  • Use measured with square pipe or 2″ pipe above
  • IP rating:IP65
  • Stainless steel casing, suitable for various severe environments, such as slightly corrosive air

Application

  • Compressed air monitoring
  • Exhaust gas emission flow monitoring
  • Special gas process
  • Semiconductor
  • electronics factory
  • Industrial process air velocity and air volume measurement

Specification

Input type Pt20/Pt300 (Air velocity) / Pt1000 (Temp.)
Measuring range 0 … 5 m/s ~ 0 … 60 m/s
Min. measuring range 0.1 m/s
Turndown ratio 500:1
Installation angle effect <3% of the measured value (When the installation angle<10°)
Output 4 … 20 mA & RS-485
0 … 10 V & RS-485
RS-485 & Impulse (1 … 500 Hz)
Preset output Out1:Air velocity
Signal connection 3-wire
Warm-up time <60 sec
Response time t90<5 sec
Load resistance Voltage output:≧100 KΩ
Current output:≦500 Ω
Accuracy ±1.5% F.S. (Option±1%)
Temp. influence 0.1% / °C
Repeatability 0.5%
Power supply DC 24 V±10%
Current consumption <0.3 A
Electrical connections M12 connector
Measuring medium Air
Operating Temp.(With body and display) 0 … +50°C
Operating Humid.(With body and display) 20 … 90%RH(Non-condensing)
Probe operating Temp. 0 … +120°C
(Increasing operating temperature will affect air velocity error)
Storage Temp. -20 … +60°C
Storage Humid. 0 … 95%(Non-condensing)
Probe pressure 16 bar
Installation Metal flange mount
R1/2″ movable thread
Inline T type tube
Flange pipe
Certification CE
IP rating IP65
Electrical protection ■ Reverse polarity ■ Over-voltage ■ Short-circuit
Material PC(Display)
Cover SUS 304(No display)
Body (including probe) SUS304
Filter SUS304
Weight 500 g(w / o cable)