E2E-X T1 AC/DC 2-Wire Models, Omron-Standard Proximity Sensor
These Proximity Sensors use high-frequency oscillation. They resist heat, chemicals, and water better than Rectangular Sensors. They are available in both shielded and unshielded models. Proximity Sensors are available in models using high-frequency oscillation to detect ferrous and non-ferrous metal objects and in capacitive models to detect non-metal objects. Models are available with environment resistance, heat resistance, resistance to chemicals, and resistance to water.
Features and Benefits
- Standard Sensors for detecting ferrous
- A wide array of variations. Ideal for a variety of
- Models with different frequencies are also available to prevent mutual
- Superior environment resistance with standard cable made of oil-resistant PVC and sensing surface made of a material that resists cutting
- Useful to help prevent
- Cable protector provided as a standard feature
Ratings and Specifications
Size Shielded Item Model | M12 | M18 | M30 | |
Shielded | ||||
E2E-X3T1 | E2E-X7T1 | E2E-X10T1 | ||
Sensing distance | 3 mm ±10% | 7 mm ±10% | 10 mm ±10% | |
Set distance | 0 to 2.4 mm | 0 to 5.6 mm | 0 to 8 mm | |
Differential travel | 10% max. of sensing distance | |||
Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on page 17.) | |||
Standard sensing object | Iron, 12 ´ 12 ´ 1 mm | Iron, 18 ´ 18 ´ 1 mm | Iron, 30 ´ 30 ´ 1 mm | |
Response frequency *1 | DC | 1 kHz | 0.5 kHz | 0.4 kHz |
AC | 25 Hz | |||
Power supply voltage (operating voltage range) *2 | 24 to 240 VDC (20 to 264 VDC) 48 to 240 VAC (40 to 264 VAC) | |||
Leakage current | DC: 1 mA max. AC: 2 mA max. | |||
Control output | Load current | 5 to 100 mA | ||
Residual voltage | DC: 6 V max. (Load current: 100 mA, Cable length: 2 m) AC: 10 V max. (Load current: 5 mA, Cable length: 2 m) | |||
Indicators | Operation indicator (red), Setting indicator (green) | |||
Operation mode (with sensing object approaching) |
NO (Refer to the timing charts under I/O Circuit Diagrams on page 21 for details.) | |||
Protection circuits | Load short-circuit protection (20 to 40 VDC only), Surge suppressor | |||
Ambient temperature range | Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | |||
Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | |||
Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | |||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | |||
Insulation resistance | 50 MÙ min. (at 500 VDC) between current-carrying parts and case | |||
Dielectric strength | 4,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | |||
Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | |||
Shock resistance | Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions | |||
Degree of protection | IEC 60529 IP67, in-house standards: oil-resistant | |||
Connection method | Pre-wired Models (Standard cable length: 2 m) | |||
Weight (packed state) | Approx. 80 g | Approx. 140 g | Approx. 190 g | |
Materials | Case | Nickel-plated brass | ||
Sensing surface | PBT | |||
Clamping nuts | Nickel-plated brass | |||
Toothed washer | Zinc-plated iron | |||
Accessories | Instruction manual |