With the ACT20C, Weidmüller is presenting a completely new type of signal converter. The compact module is equipped with an Ethernet connection and provides, in addition to signals, precise information on the status of sensors, signal processing, and cabling.

ACT20C, as a signal converter, isolates, scales, and converts analog current and voltage signals; it can be configured directly with the "WI-Manager" software or via an Ethernet network. The software is based on the supplier-independent FDT/DTM technology.

The ACT20C has been designed specifically for process automation in order to continue forward measured values and status information to networked devices. During standard operation, malfunction, maintenance, or configuration via the network, this allows a precise display of the current status.

In case of error, the ACT20C supplies precise information for error analysis and can therefore contribute to higher system availability.

Specifications

Technical Data

Dimensions and weights

  • Length : 119.2 mm
  • Width : 22.5 mm
  • Depth : 113.6 mm
  • Weight : 180 g
  • Length (inches) : 4.693 inch
  • Width (inches) : 0.886 inch
  • Depth (inches) : 4.472 inch
  • Net weight : 169 g

Temperatures

  • Humidity : 0...95 % (no condensation)
  • Operating temperature : min. -20 °C
  • Storage temperature : min. -20 °C
  • Storage temperature : -20 °C...85 °C
  • Operating temperature : max. 70 °C
  • Storage temperature : max. 85 °C
  • Operating temperature : -20 °C...70 °C

Environmental Product Compliance 

  • REACH SVHC : Lead 7439-92-1

Signal processing

  • Condition Monitoring
    Process value: sensor value, the output value
  • Diagnostics
    Device status, Short-circuit (input/output), Cable break (input/output), Overload (sensor/output)
  • Limit-value monitoring
    Process alarms with adjustable delay and hysteresis
  • Protocol
    FDT/DTM, Modbus/TCP
  • Transfer functions
    Linear, Inverse

Communication

  • Addressing
    DHCP or manual adjustment
  • Configuration
    FDT/DTM (Ethernet or service interface)
  • Interface
    RJ45: female-female, Cat.5 to 100 MHz, Jack plug for CBX200
  • Protocol
    FDT/DTM, Modbus/TCP
  • RJ45 ports
    10/100BaseT(X), auto negotiation

     Another Article:

Input

  • Number of inputs : 1
  • Sensor supply : > 17 V DC at 20 mA
  • Input voltage : 0(2)…10 V
  • Input current : 0...20 mA, 4...20 mA

Output

  • Number of outputs : 1
  • Output voltage : note 0...10 V
  • Output current : 0...20 mA, 4...20 mA
  • Load impedance voltage : ≥ 10 kΩ
  • Load impedance current : ≤ 500 Ω

General data

  • Accuracy
    < 0.15% end value (+0.05% > 55 °C), Current: 1 uA / 30 uA (+ 10 uA >55°C), Voltage: 1 mV / 15 mV (+ 5 mV > 55°C)
  • Configuration
    FDT/DTM (Ethernet or service interface)
  • Galvanic isolation
    4-way isolator;, between input / output / power supply / Ethernet
  • Power consumption
    ≤ 3.5 W
  • Rail
    TS 35
  • Temperature coefficient
    ≤ 0.01 % / °C
  • Voltage supply
    24 V DC ± 25 %

Insulation coordination 

  • EMC standards
    EN 61326-1:2006
  • Galvanic isolation
    4-way isolator;, between input / output / power supply / Ethernet
  • Pollution severity
    2
  • Rated voltage ⁄ test voltage: Ethernet interface to supply ⁄ functional earth tosupply ⁄ Ethernet interface
    31.2 V DC / 0.9 kV rmsin secondary electrical circuits, basic insulation
  • Rated voltage ⁄ test voltage: functional earth to input ⁄ output
    300 Vrms / 1.1 kV rms in secondary electrical circuits, basic insulation
  • Rated voltage ⁄ test voltage: input/ output to output/input ⁄ supply⁄ Ethernet interface
    300 Vrms / 1.7 kV rmsin secondary electrical circuits, reinforced insulation
  • Recommendations
    Namur NE43, Namur NE44, Namur NE107

Insulation coordination 

  • EMC standards
    EN 61326-1:2006
  • Galvanic isolation
    4-way isolator;, between input / output / power supply / Ethernet
  • Pollution severity
    2
  • Rated voltage ⁄ test voltage: Ethernet interface to supply ⁄ functional earth to supply ⁄ Ethernet interface
    31.2 V DC / 0.9 kV rmsin secondary electrical circuits, basic insulation
  • Rated voltage ⁄ test voltage: functional earth to input ⁄ output
    300 Vrms / 1.1 kV rms in secondary electrical circuits, basic insulation
  • Rated voltage ⁄ test voltage: input/output to output/input ⁄ supply⁄ Ethernet interface
    300 Vrms / 1.7 kV rmsin secondary electrical circuits, reinforced insulation
  • Recommendations
    Namur NE43, Namur
    NE44, Namur NE107

Connection data 

  • Type of connection : Screw connection/ RJ45 plug-in connector
  • Tightening torque, min : 0.4 Nm
  • Tightening torque, max : 0.6 Nm Clamping range, rated connection 1.5 mm²
  • Clamping range : min. 0.5 mm² Clamping range, max. 2.5 mm²
  • Wire connection cross section AWG, min : AWG 30
  • Wire connection cross section AWG, max : AWG 14
  • Wire cross-section, solid, min : 0.5 mm² Wire cross-section, solid, max. 2.5 mm²

Classifications

  • ETIM 6.0 : EC002653
  • ETIM 7.0 : EC002653
  • eClass 9.0 : 27-21-01-20
  • eClass 9.1 : 27-21-01-90
  • eClass 10.0 : 27-21-01-20

Approvals

  • Approvals : EAC
  • Approvals : DNVGL;
  • ROHS : Conform

Download Datasheet: Weidmuller ACT20C Network-compatible Signal Converters

Reference : weidmueller

Berbagi:  

Komentar

Articles