IT600 Series SMC Electro Pneumatic Transducer

SMC IT600 Electro-Pneumatic Transducer
  • The air pressure in proportion to the current signal can be output.
    Can be used as input pressure signal in combination with the pneumatic-pneumatic positioner.
  • Wide output pressure range/0.02 to 0.6 MPa.
    The maximum pressure can be set freely through the span adjustment.
  • Independent electric unit/Explosion-proof (flameproof) construction.
    The span adjustment, zero-point adjustment, and inspection maintenance can be performed with the body cover removed even in a hazardous place where the explosion or fire may occur.
  • Easy span adjustment
    As the span adjustment mechanism uses a vector mechanism, the span adjustment can be performed smoothly.

Principle of Operation

When the input current increases, armature (1) in the torque motor will be subjected to a clockwise torque, pushing flapper lever (2) to the left. As a result, the clearance of nozzle flapper (3) will increase and the nozzle back pressure will decrease. This moves exhaust valve (10) of pilot valve (5) to the left, causing the output air pressure of OUT1 to increase.

The output pressure thus increased is passed through the path inside the pilot valve to pressure sensing bellows (6), where it is converted to the force. This force acts on vector mechanism (7) via lever (11). Because the force will balance the force generated by means of the input current at lever fulcrum (12), the output air pressure proportional to the input current will be obtained.

Gain suppression spring (8) functions to immediately feedback the movement of the exhaust valve to the flapper lever, thereby contributing to loop stability.Zero point and span adjustments are performed by varying the tension force of zero adjusting spring (9) and the angle of the vector mechanism, respectively.

Principle of electro pneumatic transducer SMC IT600 Series

Specification1)

ModelIT600IT601
Low pressureHigh pressure
Input current4 to 20 mA DC
Input impedance235 Ω±15 Ω (4 to 20 mA DC)
Supply air pressure0.14 to 0.24 MPa0.24 toC 0.7 MPa
Output pressure0.02 to 0.1 MPa
(Max. 0.2 MPa)
0.04 to 0.2 MPa
(Max. 0.6 MPa)
LinearityWithin ±1.0% F.S.
HysteresisWithin 0.75% F.S.
RepeatabilityWithin ±0.5% F.S.
Air consumption2)

7 L/min (ANR)
(SUP = 0.14 MPa)

22 L/min (ANR)
(SUP = 0.7 MPa)

Ambient and fluid temperature–10 to 60°C
Air connection portRc1/4 female thread
Electrical connectionG1/2 female thread
Explosion-proof constructionExplosion-proof (flameproof) construction d2G4 (Certificate no. T28926)
MaterialAluminum die-cast body
Weight3 kg

1) Specification values are given at normal temperature (20°C).
2) Air consumption is due to exhaust from nozzle. And (ANR) indicates JIS B0120 standard air.

Replacement Parts

Part no.DescriptionNote
P255010-1Pilot valve unitIT600
P255010-19Pilot valve unitIT601

Download Datasheet: SMC IT600 Electro-Pneumatic Transducer

Berbagi:  