The FlowCERT open channel flow meter provides comprehensive flow monitoring with data logging and control functions for a complete range of flumes and weirs. It is compatible with a range of sensors in order to create a flow metering system to suit your application.
Features
- Easy prompt setup
- Standard on-board memory gives 1-year log at 10-minute intervals
- 5 control/alarm relays
- Flow totalisation and outputs
- Universal flow calculation (32 setpoints)
- Penstock control using step time
- Modbus and Profibus options
Specifications
Technical Specification
Physical
Sensor body dimensions: |
235 x 184 x 120mm (9.25 x 7.24 x 4.72in) |
Sensor body weight: |
Nominal 1kg (2.2lbs) |
Enclosure material/Description: |
Polycarbonate, flame resistant to UL91 |
Cable entry detail: |
10 cable entry knockouts, 1 x M16, 5 x M20 underside, 4 x
18mm dia (PG11) at rear |
Transducer cable extensions: |
2-core screened |
Maximum separation: |
Up to 1000m (3280ft) |
Environmental
Enclosure protection: |
IP65 / NEMA 4X |
Max. and min. temperature (electronics): |
-20°C to +50°C (-4°F to +120°F) |
Approvals
CE approval: |
Listed in the Certificate of Conformity within the manual |
Flammable atmosphere approval: |
Safe area: compatible with approved dB transducers |
Performance
Accuracy/Repeatability: |
Dependent on the application and sensor used. |
Resolution: |
Dependent on the application and sensor used. |
Min. & max. range: |
0 - 15m (49ft). Dependent on the sensor used. |
Rate response: |
Fully adjustable |
Echo processing: |
DATEM (Digital Adaptive Tracking of Echo Movement) |
Outputs
Analog outputs: |
2x Isolated (floating) output (to 150V) of 4-20mA or
0-20mA into 500Ω (user programmable and adjustable) 1μa resolution |
Digital output: |
Full Duplex RS232 |
Volt free contacts, number & rating: |
5 form “C” (SPDT) rated at 5A at 115V/240Vac |
Display |
6 digits plus 12 charact text, plus bar graph with
direction indicators, remote communicator identifier and program/run/test
mode indicators |
Input
Analog inputs: |
Isolated (floating) input (to 150V) of 4-20mA or 0-20mA
source or sink, open circuit voltage (source) 33V, 22V at 4mA, 14V at 20mA
(user programmable and adjustable) 0.1% resolution |
Velocity input: |
Via RS485 digital communications interface |
Programming
On-board programming |
By integral keypad |
PC programming: |
Via RS232 |
Programming security: |
Via passcode (user selectable and adjustable) |
Programmed data integrity: |
Via non-volatile RAM, plus backup |
Supply
Power supply: |
115Vac +5% / -10% 50/60Hz, 230Vac +5% / -10% 50/60Hz,
22-28Vdc, 10W maximum power (typically 6W) |
Fuses: |
100mA at 230Vac, 200mA at 115Vac |
Download Datasheet: FlowCERT Pulsar Open Chanel Flow Meter
Reference: www.pulsar-pm.com
Another Articles:- MicroFlow-i Pulsar Sewer Overflow
- Pulsar's Ultimate Controller
- MicroFlow Pulsar Velocity Sensor
- dBi HART Transducer Series (4-20mA loop powered) Pulsar HART Transducers
- dBMACH3 & dB3 with Double Sun Shields Pulsar Flow Transducers
Komentar
Posting Komentar
Informasi Pilihan Identitas:
Google/Blogger : Khusus yang punya Account Blogger.
Lainnya : Jika tidak punya account blogger namun punya alamat Blog atau Website.
Anonim :