Electromagnetic Flow Converter AMC2100E Series converter is a microprocessor based intelligent transmitter that can be paired with any of the Alia AMF series. The unit features multiple display parameters including flow rate, flow total, diagnostics, programming, and troubleshooting. AMC 2100E series converter with temperature/energy.
AMC2100E Series
Electromagnetic AMC2100E Series Converter With temperature/energy function can be used with AMF series flowmeter in both compact or separate versions.
Electromagnetic Flow Converter AMC2100E Series Features
- Four line LCD display Flowrate/Energy/Totalizer
- Accuracy of +/-0.4% of reading
- Bi-directional flow measurement, current and pulse output
- Large digital display, With temperature/energy function
- 99 times records for power on/off
- MODBUS/HART communication
Electromagnetic AMC2100E Series Specifications
Excitation: | Keyboard: |
Square wave | 4 keys from external for programming |
Display: | and display control. |
4 lines LCD with backlight | Low Flow Cutoff: |
Line 1 | 0 to 9.9 % |
Date and Time | Datalogger Function: |
Line 2 | 99 times records for power on/off |
6 digit flowrate | Record Data: |
7 digit energy value | Date/Time when Power on/off |
Fault code | 99 years flow rate/energy/ |
Supply temperature | Temperature / Total flow / Total energy |
Line 3 | One Record Data per Hour |
9 digit totalizer for forwarding/ reverse flow | Damping: |
9 digit totalizer for heat / cold energy | 0.1 to 99.9 Second |
Fault code content | Self Diagnosis: |
Return temperature | The following error message is |
Line 4 | indicated during application |
Differential temperature | – Coil fail |
Unit | – Power fail |
L/S, L/M, L/H, M3/S, M3/L, M3/H | – Output overaged |
KW, MW, KJ/H, MJ/H, GJ/H | – Internal error |
Measuring Range: | – Overflow |
Min. 0 to 0.15 m/s | – Empty pipe |
Max. 0 to 15 m/s | Cable Entry: |
Accuracy: | PG11 |
+/-0.4% of reading (Velocity >= 0.5 m/s) | Protection Class: |
+/-0.002 m/s (Velocity < 0.5 m/s) | IP 65 |
Repeatability: | Ambient Temperature: |
+/-0.1% of reading | -25 to +65 oC |
Current Output: | Material: |
4-20 mA (Isolated) | Aluminum Alloy |
Load | Temperature Input: |
Max. 600 | PT1000, 2 wire |
Pulse output: | Power Supply: |
Open collector | 90-260 VAC, 50/60 Hz |
Rating | 24 VDC +/- 10% (Option) |
3 to 30 VDC, 20 mA Max. | Power Consumption: |
Pulse Rate: | 3-17 W (depending on the sensor size) |
1)Scale pulse, (Pulse/M3, Pulse/L, Other) | Weight: |
2)Frequency, 0-5000 Hz | 1.4 Kg |
Communication: | Mounting: |
RS 485(MODBUS Protocol) | Wall mounting |
HART signal | Bracket on 2″ pipe |
Data Storage: | |
Operation parameters and totalization | |
figures are stored by EEPROM for more than 10 years | |