Hydrostatic Level Transmitter MEMPRO Ex C
Bamo Measures Sas has been founded in 1978. Its capital is now 400 000 Euros. Since the beginning, the company has undergone a rapid development centring on industrial pH-meters and conductivity meters. Bamo is now well-known as a leader on the French market.
Since 1990, new developments in the Level Measure have given a new spring in the export. To its own production range, the company holds numerous agencies of foreign companies in Europe and all over the world. So we are offering a complete line with always the best possible service.
Bamo is a company that comes from France. This company selling some product. The product of Bamo such as pH and ORP; Chlorine, disinfection; Data processors; Conductivity; Water hardness; Turbidity; Oxygen; Level; Temperature; Flow; Pressure; Plastic valves; Metal valves.
Hydrostatic Level Transmitter MEMPRO Ex C
The MEMPRO Ex C measuring instrument operates in accordance with the Pitot static principles, i.e. the level signal is proportional to the hydrostatic pressure in a measuring tube plunged into the liquid. It is used for measuring fill-levels of flammable liquids. The device is approved for use in danger zone 0 for flammable media assigned to explosion group IIC. The MEMPRO Ex C fill-level transmitter is used as a passive 2-pole device in intrinsically safe circuits. It converts the backpressure signal into a load independent current within a range of 4 to 20 mA.
Features
- Fill level monitoring in ATEX Ex area
- For flammable liquids
- No moving parts
- Accurate and reliable measurement
- Output signal 4-20 mA, 2 wires
- Free from fluid viscosity or conductivity
- Scales: up to 4000 mm
- ATEX certification
Application
For measuring the fill level of tank (atmospheric pressure) with an Ex area requirement. The device is suitable for flammable liquids and for use in ATEX Ex area (see the agreements herein after). The sensor (ceramic) is in contact with the vapours not directly with the fluid.
Specification
Scales: | 0 to 1000 mm Water Column |
0 to 2000 mm Water Column | |
0 to 4000 mm Water Column | |
Accuracy: | < 1% Full scale |
Process connections: | BSP 1" |
Sleeve nut 1 1/2” | |
Materials: | Stainless steel 1.4571 |
Output signal: | 4-20 mA |
Ambient temperature: | -20 ... +70 °C (equipment group 2) |
-20...+55° C (equipment group 1/2) | |
Pressure | Atmospheric |
Electric connection: | Acc. to ATEX requirement – special cable |
with a pressure compensating tubing | |
Sensor: | Ceramic; Capacitive; With automatic |
temperature compensation | |
Certification: | TÜV 04 ATEX 2420 |
Agreements: | Ex II 2 G EEx ia II C T6 |
Ex II 1/2 G EEx ia II C T6 | |
CE Marks: | EMC (89/336/ECC) |
Download Data Sheet: Hydrostatic Level Transmitter MEMPRO Ex C
Ref: bamo.eu
Komentar
Posting Komentar
Informasi Pilihan Identitas:
Google/Blogger : Khusus yang punya Account Blogger.
Lainnya : Jika tidak punya account blogger namun punya alamat Blog atau Website.
Anonim :