Bamo Resistive Level Probe STE

Bamo Resistive Level Probe STE

Bamo Measures Sas has been founded in 1978. Its capital is now 400 000 Euros. Since the beginning, the company has undergone a rapid development centering on industrial pH-meters and conductivity meters. Bamo is now well-known as a leader in the French market.

Since 1990, new developments in the Level Measure have given a new spring in the export. To its own product range, the company holds numerous agencies of foreign companies in Europe and all over the world. So we are offering a complete line with always the best possible service.

Bamo is a company that comes from France. This company selling some product. The product of Bamo such as pH and ORP; Chlorine, disinfection; Data processors; Conductivity; Water hardness; Turbidity; Oxygen; Level; Temperature; Flow; Pressure; Plastic valves; Metal valves.

Bamo Resistive Level Probe STE | Descriptions

The STE level probe in combination with a relay ES2001 detects the level of electrically conductive liquids. According to the model, up to 5 levels may be triggered (using the tank as the reference electrode) Provide a reference electrode if the tank is made of insulating material. These STE probes are not suitable for liquids with hydrocarbons or grease or for any other application where an insulating layer may deposit on the electrodes.

Features

  • For level control
  • Applications with conductive liquids
  • 1 to 5 Detection electrodes
  • Level regulation with relays ES2001

Application

  • Level control in open or closed vessels
  • Alarm for excess or lack of liquid (leak detection, empty piping, dry-pump prevention, etc.)
  • Fill or drain function with ES 2001 relay

Another Article:

Specification

ElectrodesUp to 5 rods, AISI 316 L (Titanium in option)
FittingPP or AISI 316
Head housingPBT glass fiber reinforced,
 IP 65 (EN 60 529), cable gland M20 x 1
Option: Partial insulationPolyolefin (heat shrinkable)
 To avoid false alarms by a conductive bridge through the
 the medium between electrodes or if the electrodes are
 long and can touch each other.
Temperature limitsAmbient: -20 ... +60 °C
 Liquid: -5 ... +100 °C (restrictions apply according the
 chemical)
Pressure limits6 bar at +20 °C
 1 bar at 100 °C
 Other pressure limits: On request
Min. L1 & L245 mm
Max. L1 ... L52000 mm
InstallationVertical on top of the tank; Never install horizontally

Ref: bamo.eu

Contact us : sales@wmablog.com or visit our E-Commerce

Download Data Sheet: Resistive Level Probe STE