The Hazardous Location Multi-Point Level Switch FLX is designed specifically for point level detection of liquids in containers. Available in a wide variety of mounting types, the FLX is appropriate for use in classified flammable liquids. Each FLX is manufactured to the user’s specifications, making it fit to work precisely according to the application requirements. Stem mounted magnetic float switches. Every bit as customizable as the FL series, the FLX is the float switch for use in hazardous locations considered Class 1 Division 1 or 2 areas by CSA for North America. Place up to seven NO/NC switch points wherever needed along the stem customized to your application. 7 custom configured NO/NC switch points for hazardous areas.
Class 1, Divisions 1 and 2
The FLX Series Level Switch is the float switch for use in hazardous locations considered Class I, Division 1 or 2 areas by CSA for North America.
Configuration Options
Pick the most effective switch point configuration for your needs. Choose between either Normally Closed or Normally Open for each switch point on the stem.
More Level Control
With up to 7 switch points, the FLX Series Level switch gives you more control. Place them wherever needed along the stem for a customized fit to your application.
Features
- cCSAus hazardous area rating
- Long switch life • Durable floats
- Shock resistant construction
- Up to seven switch points
Specification
Performance | |
Switch Points | Up to 7 NO/NC |
Custom Configuration | |
Connectivity | |
Outputs | NO, NC |
Physical | |
Mount & Stem Materials | 316L SS |
Float Materials | 316L SS |
Max Length | 153 in. |
Electrical | |
Switch Rating | 50 VA, 180 VA |
Max Current | |
0.5 A AC | |
Max Voltage | CI, D1 - 24 VDC / 220 VAC |
CI, Z1 - 24 VDC | |
CI, D2 - 220 VAC | |
Approvals | |
Certifications | CSA Class I, Div. 1, Groups C & D T3 (Ta 40°C) |
CSA Ex d, IIB T3; Class I, Zone 1, AEx d, IIB T3 (Ta 40°C) | |
CSA Class I, Div. 2, Groups C & D T3 (Ta 85°C) | |
Environmental | |
Maximum Certification Temperature | Class I, Div. 1: 40° C |
Class I, Div. 2: 85° C |
Download Data Sheet: Hazardous Location Multi-Point Level Switch FLX