The ACT20C series was specially developed for applications with continuous processes. It enables the continuous monitoring of diagnostic, device, and process information (“condition monitoring”). Several ACT20C components form a station that consists of an ACT20C Ethernet gateway, communicative ACT20C signal converters, and an ACT20C bus termination terminal.
Specifications
Technical Data
Dimensions and weights
- Height : 117.2 mm
- Width : 22.5 mm
- Depth : 113.6 mm
- Height (inches) : 4.614 inch
- Width (inches) : 0.886 inch
- Depth (inches) : 4.472 inch
- Net weight : 150 g
Temperatures
- Humidity : 5...95 %, no condensation
- Operating temperature : min. -25 °C
- Storage temperature : min. -40 °C
- Ambient temperature : -25 °C...+60 °C
- Operating temperature : max. 60 °C
- Storage temperature : max. 85 °C
- Operating temperature : -20 °C...70 °C
- Storage temperature : -40 °C...85 °C
Probability of failure
- MTTF : 160 Years
Environmental Product Compliance
- REACH SVHC : Lead 7439-92-1
Communication
- Addressing
DHCP or manual adjustment - Configuration
With FDT/DTM software, DHCP - InterfaceEthernet 10/100 Base T, Jack plug for CBX200, Communication via CH20M railbus with all current measuring transducers (ACT20CCMT-x)
- Protocol
Modbus/TCP, DHCP Server/Client - RJ45 ports
10/100BaseT(X), auto-negotiation
Another Article: |
Input
- Type : receives data via the CH20M rail bus from several ACT20C-CMT communicative current-measuring transducers.
General data
- Configuration
With FDT/DTM software, DHCP - Power consumption
1.5 W - Rail
TS 35 - Voltage supply
18.0 … 31.2 V DC
Insulation coordination
- EMC standards
IEC 61326-1 - Pollution severity
2 - Impulse withstand voltage
0,5 kV (1.2/50 μs) - Surge voltage category
II - Rated voltage ⁄ test voltage: Ethernet interface to supply ⁄ functional earth to Supply ⁄ Ethernet interface30 V AC RMS
Connection data
- Type of connection : Screw connection/ RJ45 plug-in connector
- Tightening torque, min : 0.5 Nm
- Tightening torque, max : 3.5 Lb In
- Clamping range, rated connection : 1.5 mm²
- Clamping range, min. : 0.5 mm²
- Clamping range, max. : 2.5 mm²
- Wire connection cross-section AWG, min. : AWG 30
- Wire connection cross-section AWG, max. : AWG 14
- Wire cross-section, solid, min. : 0.5 mm²
- Wire cross-section, solid, max. : 2.5 mm²
- Wire connection cross-section, finely stranded, min. : 0.5 mm²
- Wire connection cross-section, finely stranded, max. : 2.5 mm²
Classifications
- ETIM 6.0 : EC002475
- ETIM 7.0 : EC002475
- eClass 9.0 : 27-21-01-23
- eClass 9.1 : 27-21-01-23
- eClass 10.0 : 27-21-01-23
Approvals
- EAC
- DNVGL
- UL
- ROHS : Conform
Download : Weidmuller ACT20C Network-compatible Current Measuring Transducers