The ACT20X-SAI-HAO/2SAI-2HAO current output isolators are suitable for controlling field devices in Ex areas, up to Zone 0. The input/output-side HART protocol transparent signal connection is implemented using 4 to 20 mA current loops. Integrated alarm contacts issue an alert in the event of a malfunction; this makes troubleshooting easier and increases system availability. The rail-mounted current output isolators are optionally available in one- or two-channel versions. With 11 mm width per channel, the devices need little space in the electrical cabinet.
Specifications (ACT20X and ACT20X-SAI-HAO-S)
Dimensions and weights
- Width : 22.5 mm
- Width (inches) : 0.886 inch
- Height : 119.2 mm
- Height (inches) : 4.693 inch
- Depth : 113.6 mm
- Depth (inches) : 4.472 inch
- Net weight : 189 g
Temperatures
- Humidity : 0...95 % (no condensation)
- Operating temperature, max. : 60 °C
- Operating temperature, min. : -20 °C
- Storage temperature, max. : 85 °C
- Storage temperature, min. : -20 °C
- Operating temperature : -20 °C...60 °C
- Storage temperature : -20 °C...85 °C
Probability of failure
- MTBF : 135 Years
Environmental Product Compliance
- REACH SVHC : Lead 7439-92-1
Rated data UL
- UL certificate : E337701.pdf
Input EX
- Input current : 4…20mA
- Input frequency : 0,5…2,5 kHz @ 3,5…23 mA bi-directional HART® signal
- Output signal in case of wire break : < 1 mA
- Voltage drop : < 2 V
- Voltage drop not powered : < 6 V
- Voltage drop powered : < 2 V
Input
- Input current : 4…20mA
- Input frequency : 0,5…2,5 kHz @ 3,5…23 mA bi-directional HART® signal
- Voltage drop : < 2 V
Output
- Type : intrinsically safe circuit
- Influence of load resistance : ≤ 0.01% of span / 100 Ω
- 2-wire supply : > 14.5 V @ 20 mA
- Output signal limit : < 28 mA
- Residual ripple (current loop) : < 7.5 mVeff
- Output current : 4…20 mA (max. 23 mA)
- Cut-off frequency (-3 dB) : 0.5…2.5 kHz @ 3.5…23 mA bi-directional HART® signal
- Load impedance current : ≤ 725 Ω
Alarm output
- Alarm function : Signal limit exceeded, Line interruption at the input, No supply voltage, Device error
- Type : Relay, 1 NO (voltage-free)
- Nominal switching voltage :
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (zone 2) - Continuous current :
≤ 0,5 A AC / 1 A DC (zone 2) - Power rating :
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2) - Hysteresis :
0.1 mA (switching threshold)
Switching thresholds 0…29.9 mA (programmable)
General specifications
- Configuration : With FDT/DTM software
- Voltage supply : 19.2…31.2 V DC
- Type of connection : Screw connection
- Power consumption : ≤ 1.0 W
- Accuracy : < 0.1% span
- Temperature coefficient : < 0.01% of span/°C (TU)
- Step response time : ≤ 5 ms
- Protection degree : IP20
- Humidity : 0...95 % (no condensation)
Insulation coordination
- EMC standards : DIN EN 61326, NE 21
- Insulation voltage : 2.6 kV (input / output)
- Rated voltage : 300 V
Data for Ex applications (ATEX)
- Voltage U0 : 28 V DC
- Current I0 : 93 mA
- Power P0 : < 650 mW
- Marking: II (1) G [Ex ia Ga] IIC/IIB/ IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Installation location : Device installed in safe area, zone 2
Safety-related basic specifications
- Demand mode : High
- Description of the "safe state" : analogue Output ≤ 3.6 mA or output ≥ 21 mA
- Device type : A
- Hardware fault tolerance (HFT) : 0
- Mean Time To Repair (MTTR) : 24 h
- Safe Failure Fraction (SFF) : 85 %
- Tproof : 5 Years
- Total failure rate for dangerous detected failures (λDD) : 127 FIT
- Total failure rate for dangerous undetected failures (λDU) : 48 FIT
- Total failure rate for safe detected failures (λSD) : 0 FIT
- Total failure rate for safe undetected failures (λSU) : 164 FIT
- Safety category : SIL 2
- Probability of outage PFH : 4.8 x 10-8 h-1
Safety-related specifications Low demand mode
- Average Probability of Failure on Demand (PFDavg) :
2.29 x 10-4 (Tproof = 1 year), 4.37 x 10-4 (Tproof = 2 years), 1.06 x 10-4 (Tproof = 5 year)
Connection data
- Type of connection : Screw connection
- Tightening torque, min. : 0.4 Nm
- Tightening torque, max. : 0.6 Nm
- Clamping range, rated connection : 2.5 mm²
- Clamping range, min. : 0.25 mm²
- Clamping range, max. : 2.5 mm²
- Wire connection cross section AWG, min. : AWG 26
- Wire connection cross section AWG, max. : AWG 12
Classifications
- ETIM 6.0 : EC002475
- ETIM 7.0 : EC002475
- eClass 9.0 : 27-21-01-23
- eClass 9.1 : 27-21-01-23
- eClass 10.0 : 27-21-01-23
- UNSPSC : 30-21-18-01
Product information
- Weidmüller provides an extended guarantee period of 36 months for this device.
Approvals
- UL, Ex, DNV, DNV-GL, EAC, FM, IECEx
- ROHS : Conform
Download Datasheet : Weidmuller HART® Transparent Driver
Reference : weidmueller.com