Bacharach ECA 450 Combustion Efficiency Analyzer

The ECA 450 is an industrial-grade analyzer ideal for professionals concerned about combustion efficiency, environmental compliance, or both. Accommodating up to seven sensors, simultaneous measurements, and calculated parameters are evaluated to ensure that industrial equipment is meeting environmental regulations while burning safely and efficiently.

The ECA 450 is designed for on-demand or semi-continuous sampling of industrial furnaces, boilers, and other industrial combustion equipment. It complies with regulations such as U.S. EPA test methods, EN 50379, CTM-030, and state/local protocols including SCAQMD.

Note: The ECA 450 calculates CO2 value based on other measured values during the combustion process. It does not measure CO2 directly.


FEATURES :

  Measures up to 7 gases simultaneously
 ( minimum O2 and CO )
 , including NOx, SOx, and combustibles

Sensors are easily replaced or upgraded in the field

Rugged suitcase design with a large, easy-to-read display

Built-in printer for instant traceability and record-keeping

Specification :

Specification

Description

Power

Internal rechargeable battery or via supplied wall adapter

Run Time

8 hours minimum

Size (H x W x D)

13.5 x 18.5 x 9 in. (34.3 x 47.0 x 22.9 cm)

Weight

25 lb. (11.3 kg)

Fuels[1]

Natural gas, coal, oil 2/4/5/6, wood, kerosene, bagasse, propane, LPG, KOKS, LEG, biofuel

Operating Conditions

Analyzer: 32 to 104 °F (0 to 40 °C), 15 to 90% RH
 (non-condensing), 1 ATM ± 10%
Probe tip[2]: 1472 °F (800 °C) maximum, 10 inH2O
 (25 bar) maximum draft

Warm-up Time

60 seconds

Memory

1000 locations

Communications

RS-232

Approvals

CE mark

[1] Depending upon combustion equation type – see manual for details

[2] For standard 12 in. probe, P/N 0024-3023

Measurement Ranges :

Measurement

Description

O2

0.1 to 20.9%

CO (H2 Compensated)

0 to 4,999 ppm

CO (High Range)

4,001 to 80,000 ppm

NO

0 to 3,500 ppm

NO2

0 to 500 ppm

SO2

0 to 4,000 ppm

Combustibles

0 to 5.00% (application dependent)

Stack Temperature

-4 to 2,400° F (-20 to 1,215° C)

Primary / Ambient Temperature

-4 to 999° F (-20 to 999° C)

Pressure / Draft

-27.7 to 27.7 inch

Calculated Ranges :

Measurement

Description

Combustion Efficiency

0.1 to 100%

Excess Air

1 to 250%

CO2

0 to fuel-dependent  maximum

NOx (NO + NO2)

0 to 4,000 ppm

NOx (Referenced to %O2)

0 to 17,000 ppm

CO (Referenced to %O2)

0 to 99,999 ppm

NO (Referenced to %O2)

0 to 14,900 ppm

NO2 (Referenced to %O2)

0 to 2,100 ppm

SOx (Referenced to %O2)

0 to 17,000 ppm

Accuracy :

Measurement

Description

O2

±0.3% O2 on the practical concentration of flue gas

Stack Temperature

±4°F from 32 to 255° F (±2°C from 0 to 124° C)
±6° F from 286 to 480° F (±3°C from 125 to 249° C)
±8° F from 481 to 752° F (±4°C from 250 to 400° C)

Primary / Ambient Air Temperature

±2° F from 32 to 212° F (±1° C from 0 to 100° C)

Pressure / Draft

±2% of reading or ± 0.02 inch, whichever is greater

CO

±5% of reading or ±10 ppm, whichever is greater than 0 to 2,000 ppm
±10% of reading from 2,001 to 4,000 ppm

NO

±5% of reading or ±5 ppm, whichever is greater than 0 to 2,000 ppm

NO2

±5% of reading or ±5 ppm, whichever is greater than 0 to 500 ppm

SO2

±5% of reading or ±10 ppm, whichever is greater than 0 to 2,000 ppm

HC

±5% of a full scale

Selectable Fuels

Natural Gas, Oil #2, 4, 5, 6, Propane, Coal, Wood, Kerosene, Bagasse

Model :

N. Amer. P/N

Description

0024-7221

ECA 450 with O2 and CO sensors and probe with 12 in. sample tube
(approximately 15 ft. total length), water trap, particulate filter, and probe stop

0024-8400

ECA 450 with O2, CO, NOx kit (NO and NO2 sensors)
and compact sample conditioner

0024-8401

ECA 450 with O2, CO, NOx & SOx kit (NO, NO2 and SO2 sensors)
and compact sample conditioner

For further info please contact us, at marketing@wmablog.com

Reference: https://www.mybacharach.com/