Beck-930 Series Differential pressure switch - Wiratama Mitra Abadi | Industrial Equipment

Breaking

3.9.19

Beck-930 Series Differential pressure switch

Adjustable differential pressure switch for monitoring overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases.
The switching pressure can be adjusted without a pressure gauge using a scaled adjustment knob. Various versions with overlapping adjustment ranges between 0.2 mbar and 50 mbar are available for this purpose. As standard, the pressure switch is equipped with a transparent cover of protection class IP54.
We have three varian such as:
  • Differential pressure switch 930 adjustable
  • Differential pressure switch 930 EX adjustable
  • Differential pressure switch 930 with UL approval adjustable
*All varians is adjustable from 20 to 5000 pascal.930-8-Beck-Differetntial-pressure-switch

Applications

Adjustable differential pressure switch for monitor ing overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases.
Possible fields of application include:
  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection flaps
  • Frost protection for heat exchangers

Version

With this pressure switch the switching pressure can be adjusted without a pressure gauge using a scaled adjustment knob.
TypeAdjustment range form --- to ---Switchig diferentialRepeatability of the switching pressure
930.8020         200 Pa10 Pa±5 %,    min. ±5 Pa
930.80B20         300 Pa10 Pa±5 %,    min. ±5 Pa
930.8430         400 Pa15 Pa±5 %,    min. ±5 Pa
930.8350         500 Pa20 Pa±2.5 %, min. ±5 Pa
930.85200       1000 Pa100 Pa±1 %,    min. ±5 Pa
930.85B100       1000 Pa100 Pa±1 %,    min. ±5 Pa
930.86500       2500 Pa150 Pa±1 %,    min. ±5 Pa
930.871000     4000 Pa250 Pa±1 %,    min. ±5 Pa
930.87B1000     5000 Pa250 Pa±1 %,    min. ±5 Pa
* typically, at beginning of setting range.
Switching pressure specifications apply to vertical installation which is also the recommended position with pressure-pipe connections pointing downwards. If the switches are installed horizontally with AMP con nection terminals uppermost, the switching values are approx. 20 Pa higher.

Specification

Baca juga: Delta-Mobrey GR2/4 Pressure Switch

Maximum operating pressure

10 kPa for all pressure ranges.

Medium

Air, non-combustible and non-aggressive gases.

Temperature range

Medium and ambient temperature from –20°C to +85°C. Storage temperature from –40°C to +85°C.

Diaphragm material

Silicone, tempered at 200°C, free of gas emissions. Other materials available on request.

Pressure connections

2 plastic pipe connection pieces (P1 and P2), external diameter 6.0 mm: P1 for connection to higher pressure (marked +) P2 for connection to lower pressure (marked –)

Housing materials

Switch body and cover of plastic.

Weight

With cover 150 g, without cover 110 g.

Mechanical working life

Over 106 switching operations.

Electrical rating

Standard version:   max. 1.5 A (0.4 A) / 250 VAC
Low-voltage version: max. 0.1 A / 24 VDC

Electrical connections

AMP flat plug 6.3x0.8 mm in accordance with DIN 46244 or push-on screw terminals. Cable conduit with cable strain relief.

Arrangement of contacts

1 Break contact 2 Operating contact 3 Power supply line

 Protection category

IP 54 with cover, IP 00 without cover.

CE Conformity

each depending on technical specification: Low Voltage Directive 2006/95/EC; RoHS Directive 2011/65/EC; Gas Appliance Directive 2009/142/EC; ATEX- Directive 2014/34/EC; ANSI UL508; CSA.

Specifications according to EN1854

Class of control and regulation function: A Deviation: ≤±15 %, min. ±10 Pa Drift: ≤±15 %