The NC200 is a compact fuzzy logic plus PID temperature controller
with J or K type thermocouple or RTD input. Multiple units (up to 247
units) can be networked together with a 4P4C modular connector. Each
unit auto-tunes on the initial setup to provide the best response for
each heater. The NC200 is powered by 90-250VAC supply and contains a
solid-state relay as its control output. The solid-state relay can drive
the heater directly through a plug-in connector. The major
Relay Rating : 7A @25 C, 3.5A @47.5 C ambient temperature,
90 ~ 250 VAC, 47 ~ 63Hz.
See Fig.16 Load derating curve
Switch ON-OFF: Zero crossing triggering
Insulation resistance: 1000 Mohms min. at 500 VDC
Dielectric strength: 2500 VAC for 1 minute.
Features
-
- Compact size
- Auto addressing, manual setting unnecessary
-
- Network up to 247 controllers
- The fastest speed, taking 1 second to update 1000 data
- Used with SCADA, HMI via Modbus RTU
- Quick connector for easy and safe wirings
Specification
Power
- 90 ~ 250 VAC, 47 ~ 63 Hz, 800VA maximum
Input
| Type | Range | Accuracy | Input Impedance |
| J | -17.8°C ~ 500 °C ( 0°F ~ 932 °F ) |
±2 °C | 1MΩ |
| K | -17.8°C ~ 500 °C ( 0°F ~ 932 °F ) |
±2 °C | 1MΩ |
| PT100 (DIN) | -17.8°C ~ 500 °C ( 0°F ~ 932 °F ) |
±1°C | 1.3KΩ |
Output (Solid state relay)
Relay Rating : 7A @25 C, 3.5A @47.5 C ambient temperature,
90 ~ 250 VAC, 47 ~ 63Hz.
See Fig.16 Load derating curve
Switch ON-OFF: Zero crossing triggering
Insulation resistance: 1000 Mohms min. at 500 VDC
Dielectric strength: 2500 VAC for 1 minute.
Data Communication
| Interface | RS-232 ( 1 unit ), RS-485 ( up to 247 units ) |
| Protocol | Modbus Protocol RTU mode |
| Address | 1 – 247 |
| Baud Rate | 2.4 ~ 38.4 Kbits/sec |
| Parity Bit | None, Even or Odd |
| Stop Bit | 1 or 2 bits |
| Communication Buffer | 64 bytes |
Control
| Control Mode | Action Reverse (heating) |
|---|---|
| PID mode | PB= 1-500 °C TI= 1-900 sec. TD= 0-300 sec. |
| Cycle time | 2 seconds |
| Manual control | 0-100% |
| Auto-tuning | Cold start and warm start |
| Power limit | 0-100% |
Environmental & Physical
| Operating Temperature | -10°C ~ 50°C |
| Storage Temperature | -40°C ~ 60°C |
| Humidity | 0 ~ 90 % RH ( non-condensing ) |
| Altitude | 2000m maximum |
| Insulation Resistance | 20 Mohms min. ( at 500 VDC ) |
| Dielectric Strength | 1350 VAC, 50/60 Hz for 1 minute |
| Vibration Resistance | 10 – 55 Hz, 10 m/s² for 2 hours |
| Shock Resistance | 200 m/s2 ( 20 g ) |
| Dimensions | NC200 — 50.3(W) x 52.4(L) x 45(H) mm |
| Weight | 112 grams |
Approval Standards
| Safety | EN61010-1 |
| Protective Class | IP 20 |
| EMC | EN61326 |