Intrinsically Safe Supply Units, Dinel-Level and Flow Measurement

INTRINSICALLY SAFE SUPPLY UNITS 

 INTRINSICALLY SAFE SUPPLY UNITS

Supply and switching units NxxU are used for energizing of NAMUR output sensors (DLS–27Xi, CPS–24Xi, etc.) located in hazardous explosive areas. Due to the state of the connected sensor, they switch their output changeover relay contact or a transistor switch. Moreover, they can provide a simple 2-state level regulation (pump-up and pump-down control).

Features

  • For energizing and state-detection of NAMUR sensors (EN 60947-5-6)
  • The connected sensor can be located in hazardous explosive areas up to zone 0
  • Relay or transistors output
  • High-frequency switching (up to 2kHz – ver. "T")
  • LED state indication
  • Power supply 230 V AC or 24 V DC
  • Mounting on DIN rail 35 mm

Features of Variants

  • NSSU – 811 Single channel unit without additional functions for supply and state detection of one NAMUR sensor. Output invariant "T" (transistor switch) or "R" (relay contact).
  • NSSU – 812 Single channel unit with LFD* system for supply and state-detection of one NAMUR sensor. Output invariant "R" (relay contact).
  • NDSU – 822 Dual channel unit without additional functions for supply and state detection of two NAMUR sensors. Output invariant "T" (transistor switch) or "R" (relay contact).
  • NLCU – 821 2-state level regulation unit using two connected limits NAMUR sensors. Output invariant "R" (relay contact).
  • NLCU – 822 2-state level regulation unit with LFD* system using two connected NAMUR sensors, protection against non-logical states of level sensors. Output invariant "R" (relay contact).

Another Article:

Specification

 NSSU–811NSSU–812NDSU–822NLCU–821NLCU–822
Number of connectable sensors11222
Failure signalization (LFD system)NOYESNONOYES
Nominal supply voltage     
Version 230 V30 ... 230 V AC/DC (+10%) 50 ÷ 60 Hz
Version 24 V10 ... 30 V AC (+10%) 50 ÷ 60 Hz; 10 ... 40 V DC (+10%)
Nominal power demand (AC / DC)4 VA / 4 W
Output open – Circuit voltage 9.2 V DC
Output current – Treshold1.55 mA (± 0.1 mA)
Current limits for LFD system-< 0.1 mA--< 0.1 mA
 -> 6 mA--> 6 mA
Allowable short-circuit time in input terminalsUnlimited
Limit parametersV; I0 = 10.4 mA; P0 = 27.3 mW; C0 = 1.8 μF; L0 = 150 mH
Safe isolation voltage Um (term. 9 - 16) 253 V
Contact voltage drop (output transistor is closed)2 V (Variant "T)
Dynamic parameters * (Triggering / Gap pulse)     
Variant "R"Min. 50 ms-Min. 50 ms--
Variant "T"Min. 250 μs-Min. 250 μs--
Max. switching frequency (Max. load / Without load) 
Variant "R"0.1 Hz / 10 Hz
Variant "T"2 kHz / 2 kHz
Output characteristic (Variant "R") 
Version 230 V250 V AC / 2 A / 100 VA; 250 V DC / 2 A / 50 W
Version 24 V40 V AC / 2 A / 80 VA; 40 V DC / 2 A / 80 W
Output characteristic (Variant "T")40 V / 50 Ma-40 V / 50 mA-
Relay contact life (Variant "R")Min. 30 x 106
Ambient temperature-20°C ... +60°C
Protection IP20
Housing materialPolylcarbonate
Material of terminals CuBe
Max. conductor size1 x 2.5 mm2
Isolating voltage (mains terminal / output) 3500 V
Weight Approx.0.2 kg
* Dynamic parameters are valid by connection to contact on input unit (impulse transmitting from gas-meter, etc.)

Download Catalog: INTRINSICALLY SAFE SUPPLY UNITS,Dinel-Level and Flow Measurement

Ref: Dinel.cz

Berbagi:  