Pulsar's Quantum 2 pump station controller provides alarms, including a unique alarm warning of 'time to spill' in critical area, and resets tripped pumps automatically.
Quantum 2 is a fully-featured pump controller, using Pulsar's non-contacting ultrasonic technology including DATEM digital echo discrimination to provide solid performance and sophisticated level management. Quantum 2 includes 10 relays (digital outputs) and 7 digital inputs, and have optional RS485 digital communications (Modbus and optional Profibus DP V0 and V1) allowing the status to be monitored and the unit to be programmed remotely. Additionally Quantum 2 has the option of a large on-board data-logging facility (256kb).
Another Article: |
Features
Features
- Highly intelligent pump controllers
- Time to spill calculation and warning
- Automatically resets tripped pumps
- Second mA output for pumped flow rate
- Easy prompt led set up
- RS485 Modbus and Profibus DP V0 and V1 options
- 10 relay outputs and 7 digital inputs
- Pump efficiency alarm function
- Peak power tariff avoidance
- This unit can also be configured using Pulsar's PC Suite software
Applications
- Pump Control
- Time to spill warning requirements
- Reduction in power cost requirements
- Pump monitoring and control
- Water and waste water
Specifications
Physical
Mounting option: | Fascia Mount |
Sensor Body Dimensions: | 200 x 112mm (7.87 x 4.41in) front, 165 x 105mm (6.49 x 4.13in) cut-out |
Weight: | Nominal 1.3kg (2.9lbs) |
Transducer cable: | Twin Screened |
Maximum Separation: | 1000m (3280ft) |
Case Material: | Stainless steel and polycarbonate, flame resistant to UL94 V0 |
Environmental
IP Rating: | IP64 |
Max. and Min. Temperature (electronics): | -20C to +55C (-4F to +131F) |
Flammable atmosphere approval: | Safe area: compatible with approved dB transducers allowing installation to zone 0 |
CE Approval: | See EC Declaration of Conformity in the manual |
UL/C-UL: | UL Listed. UL Listed to Canadian safety standards. Certificate Number: E257330 |
Power Supply: | 115V ac +5%/ -10% 50/60Hz, 220V ac +5%/ -10%, 18-36V dc |
Performance
Accuracy: | +0.25% of the measured range or 6mm whichever is greater |
Resolution: | dBMACH3 0.25mm, dB3 0.5mm, dB6 and dB10 1mm, dB15 1.5mm, db25 2.5mm, dB40 5mm |
Range: | Depending upon transducer, from 125mm to 40m (0.41-130ft) |
Echo Processing: | Patented DATEM (Digital Active Tracking of Echo Movement) |
Digital Communications: | RS485 Modbus or Profibus DP V0 or V1 |
Outputs/Inputs
Volt-free contacts: | 10 in total. Relays 1-5 form C (SPDT 5A, 220V ac. Relays 6-10 form C (SPDT) 3A, 220V ac |
Digital Inputs: | 7 No or NC with 24V dc internal supply, available max. 20mA |
Analogue output (adjustable): | 2 off Isolated output of 4-20mA or 0-20mA into 500Ω (user programmable and adjustable) 0.1% resolution |
Analogue input: | Isolated input for loop powered device. 4-20mA source. NB: Active input on request |
Serial Output: | RS232 via RJ11 port |
Display: | 6 digits plus 12 character text, plus bargraph with direction indicators, remote communicator idintifier and program/run/test mode indicators |
Programming
On-Board Programming: | Standard with integral keypad |
PC Programming: | Via RS232 (RJ11 port) |
Programming Security: | Via password (user selectable and adjustable) |
Programmed Data Integrity: | Via non-volatile RAM, plus backup |