Tracer 1000™ LTT1-2G 2nd (up to 80ft) Radar Level Transmitter

 Tracer 1000™ LTT1-2G 2nd Generation Radar Level Transmitter (up to 80ft) 

Tracer 1000™ LTT1-2G 2nd Generation Radar Level Transmitter (up to 80ft)

Featuring TDR (Time Domain Reflectometry) technology, the Tracer 1000™ second-generation Guided Wave Radar level transmitter provides continuous level measurement in liquids, solids, and slurries. This innovative device has almost no installation restrictions in tanks, silo, and bins up to 80 feet. The Tracer 1000™ 2G has a fully isolated 4-20 mA output that can be scaled for tank level or distance. The unit requires 18 to 30 VDC power.

The 4-wire device comes standard with an RS-485 COMMS output that can be connected to the Tracer Talker™ software for custom configurations and detailed level processing analysis. The Tracer 1000™ 2G ships pre-calibrated precisely for the customer’s application for quick installation and setup. If adjustment is needed in the field the RS485 Communication Tool and Tracer Talker™ software is recommended. TDR technology is not affected by pressure, vacuum, temperature, viscosity, foam, or dust. Changes in dielectric constant or coating of the probe do not affect the level measurement due to the dynamic sensing technology programmed into the artificial intelligence of the Tracer 1000™ 2G GWR level transmitter

Features and benefits

  • Revolutionary TDR Technology
  • Auto Calibration to any dielectric
  • Precise continuous level measurement
  • Measures liquids, slurries, and solids
  • Highly robust measurement due to the 4-wire design and innovative signal analysis and constant disturbance signal suppression
  • Measures up to 80 feet
  • Pre-calibrated from factory for easy installation
  • High-temperature applications
  • Programmable fail-safe mode
  • RS485 Communication Tool and Software are available for purchase if calibration adjustments are required

Primary Area of Applications

  • Chemical / Petrochemicals
  • Energy
  • Food & Beverages
  • Plastic Pellets
  • Minerals & Mining
  • Oil & Gas
  • Pharmaceutical
  • Pulp & Paper
  • Wastewater
  • Transport
  • Overflow Protection
  • Asphalt Blending Tanks
  • Alum and Wax Tanks
  • Sand and Gravel
  • Primary and Secondary Sludge Clarifiers
  • Fresh Cooking Oil
  • Used Cooking Oil

Another Article:

Specification

 

Signal Output

Isolated 4-20 mA (750 ohms @24Vdc

User Voltage Supply, 250 ohms internally driven)

 

Fail-Safe Output

3.8 mA, 4 mA, Last Known, 20 mA, 20.2 mA
Operating Voltage12-30 Vdc (residual ripple no greater than 100 mV)
Power Consumption<3W @ 24 Vdc

 

 

Communications

RS485 Modbus

(RS485 activation required Tracer Talker™ Communication Software and Tool).

 

Signal Wiring

Recommended Signal Output and Communications Output is twisted shielded pairs, 20-18 AWG
Measurement Range

1.2’ to 80’ with minimum dielectric

constant of 0.3

Resolution0.0008"
Accuracy+/- 0.039” ( 1 mm) or 0.02% of the measured distance, whichever is greatest.
Update Interval100 samples/sec/updated <100 millisec.
Ambient Temp. Effect

 

+/- 0.005”/K of a measured value

Repeatability+/- 0.02” (0.5mm)

 

Maximum Operating Temperature

Electronics: -40º to 158ºF (-40 to 70ºC) Process/Probe: -40º to 398ºF standard

-50º to 593ºF with Temp. Extender Option

Maximum Operating Pressure-14.50 PSI to 580 PSI
Process Connection/ Type

Standard: 1.50" MNPT

Option:      1.50" ANSI 150lb. Flange

 

 

Probe Type/Diameter

Rod Probe: 316 Stainless Steel, 0.25"

diameter

Wire Cable Probe: 316 Stainless Steel,

0.195" diameter Weighted Assembly: 0.75" diameter

Tensile Load4,270 lbs

 

Enclosure

NEMA 6: Coated Epoxy Aluminum with IP67 Sealing
Cable Entries(2) 1/2" NPT Conduit Entries

 

Approvals

A22 ATEX Grp II Cat 3 GD T75°C IP67

Tamb -40°C to 65°C

Download Datasheet: Tracer 1000™ LTT1-2G 2nd Generation Radar Level Transmitter (up to 80ft), Flocorp