Dwyer Series 2000-HA High Accuracy Magnehelic® Differential Pressure Gage

 Dwyer Company Headquarters is in Michigan City, Indiana. Dwyer uses advances computer modeling software to simulate real world situations, creating more accurate measurement techniques in our products. Innovative product designs have been recognized by industry experts, including ACHR Dealer Design Awards in the Testing and Monitoring category for 2014 and 2015.

Dwyer has invested in state of the art research and development facilities for best in class product testing and verification. Dwyer has a long history of innovation in designing and manufacturing our own measurement sensors that provide superior product performance.



Series 2000-HA High Accuracy Magnehelic® Differential Pressure Gage

Known for quality, reliability and accuracy, Dwyer designs and manufactures a full-line of Controllers, Data Loggers, Gages, Manometers, Monitors, Remote Displays, Switches, Transmitters, and Accessories to measure, monitor and control pressure, air velocity, flow, fan pressure, duct, and more.

Dwyer’s wide selection extends to Gages, Transmitters, Switches, Data Loggers, and Monitors for Differential Pressure. Dwyer manufactures a range of dial and digital gages to reliably measure and display pressure difference, between two pressure sources using gas or liquid in a process flow.

Pressure, flow and piston-type gages are all found within this category. Clean design, small size and low cost with enough accuracy for all but the most demanding applications, these gages are the best around. Gages are indicators for the difference between two pressures or simply a single pressure.

The Series 2000-HA High Accuracy Magnehelic® Differential Pressure Gage is twice as accurate as the standard Magnehelic® gage. The well-engineered High Accuracy Magnehelic® Gage offers a mirrored overlay as standard in order to eliminate any parallax error when taking measurements. A six point calibration certificate is included with each high accuracy model. The rugged IP67 casing helps fully protect against dust and water ingress. The redesigned corrosion resistant brushed 304 stainless steel bezel option offers a clean tapered design, yet minimizes the possibility of any dust accumulation on the edges.

Features

  • Accurate within 1%
  • Mirrored scale overlay eliminates parallax error
  • Six point calibration certificate included
  • IP67 - Fully protects against dust and immersion
  • Optional corrosion resistant brushed 304 SS bezel

Application

  • Clean room positive pressure indication
  • Filter monitoring
  • Air velocity with Dwyer pitot tube
  • Blower vacuum monitoring
  • Fan pressure indication
  • Duct, room, or building pressures

Another Article:

Specification

ServiceAir and non-combustible, compatible gases (natural gas option available). Note: May be used with hydrogen. Order a Buna-N diaphragm. Pressures must be less than 35 psi.
Wetted MaterialsConsult Factory.
HousingDie cast aluminum case and bezel with acrylic cover. Exterior finish is coated gray to withstand 168 hour salt spray corrosion test.
Accuracy±1% FS (±1.5% on -0, -100PA, -125PA, -10MM and ±2% on -00, -60PA, -6MM ranges) throughout range at 70°F (21.1°C).
Pressure Limits-20 in Hg to 15 psig (-0.677 bar to 1.034 bar).
OverpressureRelief plug opens at approximately 25 psig (1.72 bar), standard gages only.
Temperature Limits20 to 140°F (-6.67 to 60°C).
Size4" (101.6 mm) diameter dial face.
Mounting OrientationDiaphragm in vertical position. Consult factory for other position orientations.
Process Connections1/8" female NPT duplicate high and low pressure taps – one pair side and one pair back.
Standard AccessoriesTwo 1/8" NPT plugs for duplicate pressure taps, two 1/8" pipe thread to rubber tubing adapters, and three flush mounting adapters with screws.
Weight1 lb 2 oz (510 g).
Agency ApprovalsMeets the technical requirements of EU Directive 2011/65/EU (RoHS II).

Download Data Sheet: Series 2000-HA High Accuracy Magnehelic® Differential Pressure Gage

Ref: dwyer-inst.com