Lake Flowstat ES Paddle Wheel Flow Meter


AW Lake is a corporate from United States of America that sell some product such as Positive Displacement Meters, Turbine Flow Meters, Tricor Coriolis Flow Meter, Lake Variable Area Flow Meter, Lake Paddle Wheel Flow Meter "Flow Stat", Monitor&Controllers. One of the product that comes from the categories of Lake Paddle Wheel Flow Meter "Flow Stat" is Lake Flowstat ES Paddle Wheel Flow Meter

Lake Flowstat ES Paddle Wheel Flow Meter

Ideal for monitoring various fluids in applications such as chillers/cooling circuits, HVAC, batching and industrial process control applications.

The FlowStat flow rate meters integrates rugged tangential turbine technology with a precision digital to analog conversion circuit hermetically encapsulated within the body of the meter. The flow meter is ideal for measuring flow rates in cooling circuits, HVAC systems and batching operations.

Advantages:

  • Value Pricing: Low cost operation combined with low cost maintenance, equals better bottom line savings form your operation.
  • Encapsulated Circuitry: Withstands the harshest environments.
  • Several Outputs Available: The standard interface is a 2-wire, 4-20mA current loop. Sensor signal may be transmitted on a low cost wire without degradation. Pulse, relay and 0-5 VDC (regulated) are also available.
  • Connects Directly to your Flow Monitoring Instruments: Can be connected directly to analog acquisition cards, chart recorders or other monitoring instruments, without external signal conditioning.

Simply Plumb and Apply Power: Comes factory calibrated to your flow range specifications.

Features:

  • Measuring Accuracy: ±2.0% of full scale
  • Flow Ranges: 0.5-15 GPM (2-60 LPM)
  • Pressure Rating: up to 150 PSI
  • Temperature Rating: 20-150°F
Repeatability: ±0.5% of full-scale

Flow Measuring Range: 0.5-15 GPM (2-60 LPM)

With optional low-flow adapter: 25-4.5 GPM (1-17 LPM)

Turn Down Ratio: 10:1

Maximum Operating Pressure: 150 PSIG

Maximum Operating Temperature: 20-150°F

Standard Calibration Fluid

  • Tap water @ 70°F Temperature (21°C),
  • 1.0 sg

Filtration Requirement: 150 Micron Filter recommended

Material Construction

Wetted ComponentsNon-Wetted Components
ComponentMaterialsComponentMaterials
CasingGlass-Filled PolypropyleneEncapsulantEpoxy
CoverClear PolycarbonateStrain ReliefNylon
SealBuna-N® (Other optionsLock RingGlass-Filled
 available) Polypropylene
ImpellerAcetal CopolymerWire InsulationHigh-Temperature
   PVC
BearingPEEK  
 (Polyetheretherketone)  
ShaftStainless Steel  

Download Data Sheet: Lake Flowstat ES Paddle Wheel Flow Meter